A DIN Rail Mount UPS with line interactive topology, the CyberPower BAS34U24V provides DC power supply, surge protection battery and backup for compact, embedded controller/server platforms, industrial computers and networking devices. Designed for building automation systems (BAS), energy management systems (EMS) and other types of facility controllers and remote facility monitors, the UPS supports distributed computing with up to 4 hours of extended battery runtime, among other industry-leading features.
The BAS34U24V comes with a three-year warranty (including coverage of batteries) and a $500,000 Connected Equipment Guarantee.
GENERAL | |
UPS Topology | Automation System |
INPUT | |
Rated Input Voltage | 100-240Vac |
Minimum Input Voltage | 90Vac |
Maximum Input Voltage | 264Vac |
Rated Input Frequency Range | 50-60Hz |
Input current @ 90Vac, Full Load | 1.5A |
CHARGER CHARACTERISTICS | |
Charging Voltage | 16.4Vdc |
Maximum Charging | 350mA |
Maximum Charging Time | 24 Hours |
Charger Auto-Restart | Yes, when utility power is restored |
External Battery Function | Yes |
BATTERY | |
Runtime at 10W | 7 Hours |
Runtime at 12W | 6 Hours |
Runtime at 15W | 4.5 Hours |
Runtime at 18W | 4 Hours |
Runtime at Max (34W) | 2 Hours |
Battery Type | Li-ion (18650) Rechargable Battery |
Battery Voltage | 14.8Vdc |
Battery Capacity | 6500mAh |
Battery Quantity | 1 |
Low Battery Warning | 13.2Vdc ± 3% |
Battery Shutdown Voltage | 12.4Vdc ± 3% |
Transfer Time | <20ms |
Battery Leakage Current | <0.5mA (@End of discharging) |
BATTERY CONT. | |||
Battery Test | Yes | ||
External Battery Pack Function | Yes | ||
PROTECTION FUNCTIONALITY | |||
Output Voltage Range | 24Vdc ± 3% | ||
Rated Output Power | 8 p Output | 24W/1A | |
2 p Output 1 | 5W/0.21A | ||
2 p Output 2 | 5W/0.21A | ||
Overcharging Voltage Protection | 17.5Vdc ± 3% | ||
Overload Protection | Output 1 | >1.17A | Output turn-off after, auto- recovery in 10s |
Output 2 | >0.29A | ||
Output 3 | >0.29A | ||
Output Short Circuit Protection | Output turn-off and auto- recovery in 10seconds | ||
Output Over Voltage Protection | Line Mode | >28.8Vdc ± 3% | Output & LED turn-off |
Battery Mode | Unit Shutdown |
PROTECTION FUNCTIONALITY CONT. | |
Battery Current Protection | 5A/250Vac fuse |
Input Surge Protection Capability | 2.5kV (K.21 basic) |
ESD Protection Capability | Air 8kV/Contact 4kV |
PHYSICAL | |
Dimensions Always (WxHxD) | 7.91” x 4.72” x 3.72” |
Weight | 2.87 lb. |
ENVIRONMENT | |
Operating Temperature | 32°F–113°F (0°C–45°C) |
Operating Relative Humidity | 0–95% (Non-condensing) |
Operation Elevation | 10,000 ft (3,000 m) |
CERTIFICATIONS | |
SAFETY | UL60950-1, CSA CS22.2 NO.60950-1-07, IEC/EN 60950-1, FCC Part 15 Class B, CISPR 22 Class B |
WARRANTY | |
Product Warranty | Three-Years Limited (Including Batteries) |
Connected Equipment Guarantee | Lifetime |
CEG Amount | $500,000 |