A rack/tower UPS with line interactive topology, the CyberPower Smart App LCD OR1500LCDRT2U provides battery backup (using simulated sine wave output) and surge protection for department servers, workgroup servers, workstations, network devices, and telecom installations without active PFC power supplies. The OR1500LCDRT2U uses Automatic Voltage Regulation (AVR) to correct minor power fluctuations without switching to battery power, which extends battery life. AVR is essential in areas where power fluctuations occur frequently. The OR1500LCDRT2U comes with a three-year warranty and a $300,000 Connected Equipment Guarantee.
Features:
GENERAL | |
UPS Topology | Line Interactive |
Energy Saving | GreenPower UPS™ Bypass |
ENERGY STAR® Qualified | Yes |
INPUT | |
Voltage | 90 – 140 VAC |
Frequency Range | 50/60 Hz ±3 Hz |
Plug Type | NEMA 5-15P |
Plug Style | Straight |
Cord Length | 10 ft |
OUTPUT | |
VA | 1,500 |
Watts | 900 |
Automatic Voltage Regulation | Yes |
On Battery Voltage | 120Vac ± 10% |
On Battery Frequency | 50/60Hz ± 1% |
On Battery Waveform | Simulated Sine Wave |
Outlet Type | NEMA 5-15R |
Outlets - Battery & Surge Protected | 8 |
Overload Protection | Internal circuitry limiting / circuit breaker |
Transfer Time | 4ms |
BATTERY | |
Runtime at Half Load | 18 minutes |
Runtime at Full Load | 6 minutes |
Battery Type | Sealed Lead-Acid |
Battery Size | 12V / 7Ah |
Battery Quantity | 4 |
User Replaceable | Yes |
Replacement Battery Cartridge | RB1270X4F |
Replacement Battery Cartridge Quantity | 1 |
Typical Recharge Time | 8 Hours |
SURGE PROTECTION & FILTERING | |
Surge Suppression | 1,840 J |
Phone RJ11 / Ethernet RJ45 | 1-In, 1-Out (Combo) |
Coax Protection RG6 | 1-In, 1-Out |
MANAGEMENT & COMMUNICATIONS | |
Multifunction LCD Panel | Displays: Current/Load Level, Runtime, Battery Level, AVR In Use, Battery In Use, Input Voltage, Output Voltage, Output Frequency, Overload, Silent Mode |
HID Compliant USB Port | Yes |
Serial Port | Yes (2x) |
Management Cable | USB Cable, Serial Cable, Phone line |
Audible Alarms | On Battery, Low Battery, Overload, Battery Missing, Fault |
Software | PowerPanel® Business Edition |
SNMP / HTTP Remote Monitoring | Yes, with optional RMCARD205 |
PHYSICAL | |
Rack Size | 2U |
Form Factor | Rack/Tower |
Dimensions (WxHxD) (in.) | 17.25 x 3.5 x 15.75 |
Weight (lbs.) | 48.4 |
ENVIRONMENTAL | |
Operating Temperature | 32° F – 95° F °F (0° C – 35° C °C) |
Operating Humidity | 0 – 95% (non-condensing) |
CERTIFICATIONS | |
Safety | UL1778, cUL, cUL 107.1 FCC DOC Class B |
Environmental | RoHS Compliant |
WARRANTY | |
Product Warranty | 3 Years Limited |
Connected Equipment Guarantee | Lifetime |
CEG Amount | $300,000 |