Minuteman - E2000RTXL2UNC - EnterprisePlus LCD Series true sine wave, extended runtime, line-interactive UPS, rack/tower/optional wallmount, LCD display
Part number:
E2000RTXL2UNC
Price:

Backup Versatility: Redefined

The EnterprisePlus LCD offers users more of what has made the series one of our best selling lines. New features include lower cost standard runtime models, an informative LCD Display, and additional outlets vs. previous models.

 

The EnterprisePlus LCD Series of UPSs offer complete protection from all electrical problems, including spikes, surges, sags, brownouts, and blackouts, in a versatile rack/tower convertible format. True sine wave electrical output ensures the best power for sensitive electronic equipment.

 

Output Power Factor All EnterprisePlus LCD models up to 1500VA come with a 0.8 power factor of which increases the watt capacity of the units. The 2000VA model has a 0.88 power factor and the 3000VA has a 0.853 power factor. Offering larger capacities in smaller UPS VA sizes reduces the overall cost of the UPS solution for a specific load requirement.

 

Output Voltage

All units in the EnterprisePlus LCD Series produce an electrical signal that does not vary from nominal voltage by more than 5%. Tightly regulating the output voltage increases the quality of power to connected equipment adding to its life expectancy, which lowers the total cost of ownership to users.

 

Total Harmonic Distortion (THD)

THD is the distortion of a normal AC electrical signal commonly causes UPS when connected loads near the capacity of the units. This distortion can cause internal heat to build up on sensitive equipment not designed to allow for these altered AC signals. The EnterprisePlus LCD UPS maintains an output AC signal, at all times and with linear loads, within 2% of a true sine wave.

 

Output Receptacle Control: The ability to extend the runtime of critical devices during an extended blackout is handled through the EnterprisePlus LCD’s load shedding function. Each model in the EnterprisePlus LCD UPS comes with two independently-circuited receptacle segments. Through the use of Minuteman’s SentryPlus software or communication with the UPS through an Ethernet connection, users can either turn on, off, or reset each segment independently of the other. By reducing the load amount on the UPS, the runtime of critical devices on the UPS battery can be extended.

 

Features:

Choose your runtime – EnterprisePlus LCD is available in Standard and Extended Runtime configurations

  • Standard Runtime Models (RT2U) utilize only internal batteries and are available at a lower cost
  • Extended Runtime Models (RTXL2U) feature the ability to add external battery packs for greatly increased runtimes
  • 0.8 & greater power factor – get increased capacity without migrating to larger models
  • Load shedding – two power banks allow equipment prioritizing for increased runtime
  • Independent Battery Bypass – provides voltage regulation with surge and spike protection even when batteries are weak or dead.
  • Virtually unlimited runtime with XL Models – no limitation on the number of external battery packs
  • Alarm Silence button on front panel
  • Flexibility in installation – rack or tower configurable; wallmount kits available
  • Small form factor – 3.5-inch (2U) rack/tower case
  • Independent battery pack chargers – reduces battery recharge times for XL Models
  • Simultaneous DB-9, USB and SNMP communications
  • Minuteman SentryHD – UPS monitoring and control software included
  • Easy to read LCD display – with load/battery meter
  • Industry leading product protection – with 3-year non-prorated warranty (including batteries)
  • Dedicated remote Emergency Power Off (EPO) port
  • 120V & 208V – 208V models available (1500 & 3000VA models)
  • RoHS 2 compliant
  • Industry-leading 3-year non-prorated warranty
 E2000RTXL2UNC 
Maximum Power Capacity (VA/Watts)2000/1760 
TopologyLine-Interactive, True Sine Wave Uninterruptible Power Supply
Power Factor 0.88 

Battery and Surge

Protected Receptacles

8 - 5-15/20R, 1 - L5-20R
Input Connection (with 10 ft power cord)5-20P
Mounting/InstallationRackmount/Tower and Wallmount
Input
Number of PhasesSingle (1Ø 2W +G)
Nominal Voltage•Voltage Range120VAC (208VAC) • 80-164VAC (150-271VAC)

Frequency Range

Acceptable Input Voltage

50/60Hz +/-6Hz Autosensing 0-165VAC (0-300VAC)
Low Voltage Transfer Point80V (150V) resets to utility power at 85V (157V) or higher
High Voltage Transfer Point164V (271V) resets to utility power at 159V (264V) or lower
Input ProtectionResettable circuit breaker
Output Non-battery Operation
Voltage Range • Voltage Regulation120VAC: 101-136VAC • -15.8% to 11.7% (208VAC: 186-236VAC) / -10.6% to +13.5%

Frequency Range •

Efficiency (Line Mode)

60Hz/50Hz ±6Hz • >97% at full load
Output Battery Operation
Nominal Voltage120/125VAC (208/240VAC)
Voltage Regulation120VAC (208VAC) ±5% until low battery warning
Frequency±0.1Hz unless synchronized to line
Voltage THD<5% at full rated linear load / <12% at full rated non-linear load
Dynamic Response • Transfer Time±10% @ 100% Load change in 30 ms
WaveformTrue Sine wave
Overload capacity110% for 20 seconds, 125% for 10 seconds, 150% shutdown immediately
ProtectionOver current, Short circuit protection and Latching shutdown
Battery System
Battery TypeSealed, non-spillable, maintenance free, valve regulated lead acid
Typical Recharge Time8 hours from total discharge to 90%
Typical Battery Life3-5 years, depending on discharge cycles and ambient temperature
System Voltage72VDC 
Battery ModuleBM0031 
Runtime: Half •Full Load (minutes)13 • 5 
Surge Protection and Filtering
Surge Energy Rating (Joules)1000J (800J)
Surge Current Capability6500Amps total
Surge Response time0ns(instananeous) normal mode: <5 ns common mode
Noise Filternormal and common mode EMI/RFI suppression
Audible Noise at 1 m (3 ft.)<60dBA 
Environmental
Temperature: Operating • Storage+32° to +104°F (0° to 40°C) • +5° to +113°F (-15° to +45°C)
Humidity: Operating/Storage95% non-condensing
Elevation: Operating•Storage0 to 10,000ft. (0 to 3,000m) • 0 to 50,000ft. (0 to 15,000 m)
Physical
Size: Net (L x W x H) in (mm)24.0 x 19.0 x 3.5 in (610.0 x 482.6 x 89.0 mm)
Size: Shipping (L x W x H) in (mm)39.4 x 23.6 x 9.1 in (1000.0 x 600.0 x 230.0 mm)

Weight: Net

Shipping

72.1 lb (32.7 kg)

88.2 lb (40.0 kg)

External Battery Packs

(XL & EXL EXTENDED RUNTIME MODELS ONLY)

Battery PackBP36RTXL BP36RTXL BP36RTXL BP72RTXL BP72RTXL BP36RTEXL BP36RTEXL BP36RTEXL BP72RTEXL BP72RTEXL
Typical Recharge Time8 hours to 90% after full load discharge
Size: Net (L x W x H)17.0 x 19.0 x 3.5 in (432.0 x 482.6 x 89.0 mm)
Size: Shipping (L x W x H)23.6 x 21.7 x 9.1 in (600.0 x 551.0 x 230.0 mm)
Weight: Net • Shipping lb (kg)56.0 lb (25.4 kg) • 66.1 lb (30.0 kg)
Regulatory Compliance (UPS and Battery Packs)
Safety and ApprovalsRoHS2 Directive 2011/65/EU, cUL, CE, FCC Class B
Warranty • Platinum ProtectionThree-years parts, labor, & battery (non-prorated); 5-year extended plans available • $100,000
Name
Description
Size
Downloads
File
Datasheet
1.8mb
File
Manual