Experience reliable power protection with our advanced online UPS series, designed for true double-conversion performance. Extend uptime indefinitely with compatible external battery packs and stay informed with a user-friendly front panel LCD. TAA-compliant for Federal, State, and Local government use, it also features output receptacle control for optimized load management. Backed by a full 3-year warranty, including batteries, for complete peace of mind.
Features:
UPS Model | EC1000RTXL2U | EC1500RTXL2U | EC2000RTXL2U | EC3000RTXL2U |
GENERAL | ||||
Topology | Double-conversion, On-line, True Sine Wave | |||
VA Rating | 1,000VA | 1,500VA | 2,000VA | 3,000VA |
Load Capacity | 900 Watts | 1,350 Watts | 1,800 Watts | 2,700 Watts |
Power Factor | 0.9 | |||
Input (10ft. power cord) | 5-15P | 5-20P | L5-30P | |
Receptacles | (6) 5-15R | (6) 5-15/20R | (6) 5-15/20R / (1) L5-30R | |
Outlet Control | (2) Independently controllable banks of (3) outlets, (L5-30R is Always On) | |||
Installation Type | Rack/Tower or Wall (with optional installation kit) | |||
INPUT | ||||
Nominal Voltage | 120VAC | |||
Acceptable Input Voltage | 0-160VAC | |||
Frequency Range | 50/60Hz, ±6Hz, Auto-sensing | |||
Power Factor Correction | ≥99% at full load | |||
Efficiency | >90% Full Load, On-line Mode (AC – AC) >96% Full Load, Economy Mode | |||
OUTPUT (NON-BATTERY OPERATION) | ||||
Voltage Default | 120VAC (110/127VAC adjustable) | |||
Voltage Regulation | ±2% of nominal voltage | |||
Frequency Range | 50/60Hz, ±6Hz | |||
Efficiency (Line Mode) | >90% (Full Load) | |||
OUTPUT (BATTERY OPERATION) | ||||
Nominal Voltage | 120VAC (110/127VAC adjustable) | |||
Voltage Regulation | Nominal ±2% (until Low Battery Warning) | |||
Frequency | 50/60Hz, ±0.2Hz (unless synchronized to utility) | |||
Voltage T.H.D. | ≤3% (Full Linear Load) | |||
BATTERIES | ||||
Battery Type | Sealed, non-spillable, maintenance-free, valve-regulated lead acid | |||
Replacement Module | BM0069 | BM0070 | BM0071 | |
Runtime (Half Load) | 10 Minutes | 15 Minutes | 10 Minutes | 10 Minutes |
Runtime (Full Load) | 2 Minutes | 5 Minutes | 3 Minutes | 3 Minutes |
Compatible Battery Packs | BP24RTXL2U BP24V72RTEXL | BP48RTXL2U BP48V36RTEXL | BP72RTXL2U BP72V24RTEXL | |
ENVIRONMENTAL | ||||
Operating Temp. (Max) | 0° to 40°C (+32° to +104°F) | |||
Operating Humidity | 10% to 90% Non-condensing | |||
Operating Elevation | 0 to 3,000m (0 to +10,000 ft.) | |||
PHYSICAL | ||||
UPS Size (LxWxH) in Inches and mm (with rack ears installed) | 16” x 18.9” x 3.5” 407 x 479 x 88mm | 19.2” x 18.9” x 3.5” 487 x 479 x 88mm | 23.7” x 18.9” x 3.5” 602 x 479 x 88mm | |
UPS Weight | 24.3 lbs. / 11 Kgs. | 44.1 lbs. / 20 Kgs. | 65.7 lbs. / 27 Kgs. | |
Battery Pack Size (LxWxH) in Inches | BP24RTXL2U: 17.3”x16.9”x3.5” BP24V72RTEXL: 17.3”x26.8”x5.3” | BP48RTXL2U: 17.3”x16.9”x3.5” BP48V36RTEXL: 17.3”x26.8”x5.3” | BP72RTXL2U: 17.3”x22.9”x3.5” BP72V24RTEXL: 17.3”x26.8”x5.3” | |
Battery Pack Weights | BP24RTXL2U: 60 lbs. / 27.2 Kgs. BP24V72RTEXL: 138.9 lbs. / 63 Kgs. | BP48RTXL2U: 60 lbs. / 27.2 Kgs. BP48V36RTEXL: 138.9 lbs. / 63 Kgs. | BP72RTXL2U: 83.3 lbs. / 37.8 Kgs. BP72V24RTEXL: 127.9 lbs. / 58 Kgs. | |
REGULATORY COMPLIANCE | ||||
Safety and Approvals | cTUVus (Conforms to UL1778 5th Edition & CSA 22.2 no. 107.3-14 /R: 2014), FCC Class A, CE certified, Energy Star 2.0, DoE 10 CFR Part 430, RoHS2 (EU Directive 2011/65/EU) |