Vivotek - NDR-240-48 - 240W Single Output Industrial DIN RAIL Power Supply, 48V
Part number:
NDR-240-48
Price:

NDR-240 is one economical slim 240W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 64mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to EN6100-3-2, the norm the European Union regulates for harmonic current.

 

NDR-240 is designed with metal housing that enhances the unit’s power dissipation. With working efficiency up to 89%, the entire series can operate at the ambient temperature between -20°C and 70°C under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV EN60950-1, and etc.) make NDR-240 a very competitive power supply solution for industrial applications.

 

Features:

  • Input 90 ~ 264 VAC
  • Output 48 VDC / 240 W
  • Rated Current: 5 A
  • UL 508 Approved
  • Cooling by free air convection
  • EN61000-6-2 industrial immunity level
  • Operating Temps -20~70°C
  • 100% full load burn-in test
  • 3-years warranty

 

Model Encoding:

  • NDR: Series Name
  • 240: Output Wattage
  • 48: Output voltage
MODEL NDR-240-48
OUTPUTDC VOLTAGE48V
RATED CURRENT5A
CURRENT RANGE0 ~ 5A
RATED POWER240W
RIPPLE & NOISE (max.) Note.2150mVp-p
VOLTAGE ADJ. RANGE48 ~ 55V
VOLTAGE TOLERANCE Note.3±1.0%
LINE REGULATION±0.5%
LOAD REGULATION±1.0%
SETUP, RISE TIME1500ms, 100ms/230VAC 3000ms, 100ms/115VAC at full load
HOLD UP TIME (Typ.)28ms/230VAC 22ms/115VAC at full load
INPUTVOLTAGE RANGE Note.490 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE47 ~ 63Hz
POWER FACTOR (Typ.)PF>0.98/115VAC, PF>0.95/230VAC at full load
EFFICIENCY (Typ.)90%
AC CURRENT (Typ.)2.5A/115VAC 1.3A/230VAC
INRUSH CURRENT (Typ.)20A/115VAC 35A/230VAC
LEAKAGE CURRENT<1mA / 240VAC
PROTECTIONOVERLOAD105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE56 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
Protection type : Shut down o/p voltage, re-power on to recoverShut down o/p voltage, recovers automatically after temperature goes down
ENVIRONMENTWORKING TEMP-20 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY-40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT±0.03%/℃ (0 ~ 50℃)
VIBRATIONComponent:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC (Note 4)SAFETY STANDARDSUL508, TUV EN60950-1 approved
WITHSTAND VOLTAGEI/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSIONCompliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
EMC IMMUNITYCompliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A
OTHERSMTBF230.2K hrs min. MIL-HDBK-217F (25℃)
DIMENSION63*125.2*113.5mm (W*H*D)
PACKING1Kg; 12pcs/13Kg/1.1CUFT